UL Type SIS Lead-Free Irradiated PE (XLPE) Hook-Up Wire

YU TAI provides our global partners with cable assembly services, including cable cutting, stripping, wire/cable crimping, to fulfill specific manufacturing needs.

UL Type SIS Lead-Free Irradiated PE (XLPE) Hook-Up Wire - HOOK-UP-WIRE
  • UL Type SIS Lead-Free Irradiated PE (XLPE) Hook-Up Wire - HOOK-UP-WIRE

UL Type SIS Lead-Free Irradiated PE (XLPE) Hook-Up Wire

Designed for the internal wiring of switchboards, terminal boards and electronic equipment, this UL Type SIS wire uses a tinned annealed copper conductor with electron-beam cross-linked polyethylene—XLPE—insulation.

The product is rated for a maximum conductor operating temperature of 90°C and a voltage of 600V. The current catalog lists AWG 14, 12, 10 and 8 and describes heat, flame, abrasion, oil and solvent resistance together with easy termination and wiring characteristics.

Product at a Glance

Wire TypeUL Type SIS
Temperature RatingMaximum conductor operating temperature: 90°C
Voltage Rating600V
Conductor MaterialTinned annealed copper
Insulation MaterialElectron-beam cross-linked polyethylene, XLPE
Catalog SizesAWG 14, 12, 10 and 8
Intended Use Internal wiring of electronic equipment, particularly terminal-board wiring
Flame Performance The current product catalog states that the wire passed the UL VW-1 vertical flame test
Allowable-Current Condition Catalog values are based on an ambient temperature of 40°C in air
Environmental DescriptionIdentified as lead-free in the current product catalog

When Should You Specify UL Type SIS Wire?

Consider this product when the equipment drawing or purchasing specification calls for:

  • UL Type SIS wire.
  • A 90°C and 600V rating.
  • Electron-beam cross-linked XLPE insulation.
  • Internal wiring of electronic equipment or terminal boards.
  • AWG 14, 12, 10 or 8.

Do not substitute this product for UL AWM 1007, UL AWM 1015 or another UL Style based only on the voltage rating. Confirm the specified wire type or style, insulation material, temperature rating, voltage rating, conductor size, flame requirement and equipment approval conditions.

Product Features

90°C and 600V Rating

The maximum conductor operating temperature is 90°C, and the rated voltage is 600V for equipment wiring designed around these operating conditions.

Electron-Beam Cross-Linked XLPE Insulation

The wire uses electron-beam cross-linked polyethylene insulation. According to the current product catalog, the material provides good resistance to heat, water, chemicals and atmospheric corrosion.

Abrasion, Oil and Solvent Resistance

Catalog-listed characteristics include resistance to abrasion, deformation, oil and solvents, together with good tensile strength and elongation.

Easier Internal Wiring and Termination

The current catalog describes a relatively small outside diameter, low weight and easy termination and wiring characteristics, supporting internal equipment layouts.

UL VW-1 Flame-Test Description

The current product catalog states that the wire passed the UL VW-1 vertical flame test. Where formal certification documents, a UL File Number or project-specific evidence are required, include the document requirements in the RFQ.

Typical Applications

  • Internal wiring of electronic equipment.
  • Terminal-board wiring.
  • Equipment wiring that specifies 90°C, 600V and XLPE insulation.
  • Internal connections requiring a tinned copper conductor.
  • Internal wiring requiring resistance to flame, abrasion, oil or solvents.

Final suitability must be confirmed against the equipment drawing, installation method, bundling condition, ambient temperature, terminal capacity and applicable safety requirements.

Conductor and Electrical Data

AWG Conductor Composition
No./mm
Conductor Diameter
mm
Nominal Insulation Thickness
mm
Max. Conductor Resistance
at 20°C, Ω/km
Catalog Allowable Current
A
Dielectric Strength
ACV/1 min
1441/0.2541.90.89.3327.43000
1265/0.2542.370.855.8837.23000
10105/0.2543.00.853.7350.13000
841/0.5113.81.352.2373.03500

The values above are based on the current product catalog. Catalog allowable-current values are based on an ambient temperature of 40°C in air. Actual conductor selection must also consider bundling, heat dissipation, terminal capacity, equipment drawings, installation conditions and applicable safety requirements.

UL Type SIS vs. UL AWM 1007 and UL AWM 1015

Decision PointUL Type SISUL AWM 1007UL AWM 1015
Insulation MaterialIrradiated cross-linked XLPEPVCPVC
Temperature Rating90°C80°C105°C
Voltage Rating600V300V600V
Primary Selection Basis Drawing specifies UL Type SIS or XLPE insulation Drawing specifies UL Style 1007 Drawing specifies UL Style 1015
Direct Substitution Do not decide based only on voltage Follow the drawing and equipment requirements Follow the drawing and equipment requirements

UL Type SIS, UL AWM 1007 and UL AWM 1015 have different insulation materials, temperature ratings and specification requirements. A shared voltage rating does not make different wire types or UL Styles automatically interchangeable.

Selection rule: First confirm the UL Type or UL Style specified on the equipment drawing. Then verify the temperature rating, voltage rating, conductor size, insulation material, flame requirement and equipment approval conditions.

View UL/CSA PVC Electronic Wire

Wire Supply and Processing Review

For SIS wire supplied in specified cut lengths or with stripping, tinning, terminal crimping or cable assembly requirements, please submit the drawing, quantity and inspection requirements. YU TAI will review product availability and processing feasibility according to the requested specifications.

Information Required for an Accurate Quote
Wire TypeUL Type SIS
AWG Size14, 12, 10 or 8
ColorRequired insulation color
Supply FormatReel, specified cut length or processed wire
Length per PiecePlease specify mm, cm or m
QuantityTotal length, number of reels or number of pieces
ApplicationTerminal board or other electronic equipment
Operating Conditions Operating voltage, ambient temperature and installation environment
Processing Requirements Cutting, stripping, tinning, crimping, terminals or wire marking
Document Requirements Datasheet, certification, environmental or purchasing documents
DestinationCountry or region
Required DateSample or production delivery target
Download

Contact Information

kaitai@yutai.com.tw

More Details